The Infralight Pro-series of ultraviolet disnfection systems uses the latest in uv lamp and ballast technology. Amalgam ultraviolet  lamps emit more than double the amount of ultraviolet  light that normal low presure lamps emit. Amalgam lamps operate at a  higher envelope temperature which means the uv output is constant through a wider temperature range. Because of this advance, amalgam lamps are successfully used  in hot water systems treating legionella, often found in hospitals nursing homes and aged care facilities. All Pro-Series uv disinfection systems utilise stable electronic ballasts to maximise lamp life and reduce power consumption. Features of the A series include UV sensor, remote monitoring with4-20mA, remote activation, off-delay operation, outdoor installation. The Pro series systems are designed for continuous flow from zero to design flow rate. If the unit experiences zero flow, the unit will switch off automatically after a preset time (factory set 2 hours). The feature saves power, extends lifetime of the lamp and prevents water or effluent passing untreated.

Standard Features on All Infralight A Systems

End of Life Dose

Infralight A series uv systems are calculated for an end of life dose of 40mJ/cm2. This means after 13000 hours of operation, the uv irradiation emiited by the lamps will be 40mJ/cm2

Chamber Material

The pressure chamber that the water or fluid passes through is made from AS316 polished stainless steel. Chambers are rated  for all commercial beverage and dairy applications. Assembly is quick and simple. The chamber is compatable with hot water and steam sanitisation processes.

IP Rating

The control cabinet is normmaly constructed from AS304 stainless steel with a standard IP rating 65. Infralight A series are designed for outdoor installations unless requested otherwise

UV Intensity Monitor

The uv intensity monitor (photometer), measures the ultraviolet light emitting from the uv lamp. The meter  indicates  UV lamp output in percent of watts, monitors ballast condition and  lamp condition. Volt free contacts allow remote monitoring of ballast and lamps. 4-20mA is standard

Remote Operation

All Systems  be triggered and monitored remotely. Remote switching requires a closed dry contact (PLC or flow switch) only.

Off-Delay Timer

When the remote switch is open, either from a PLC or  flow switch etc, the UV system will remain ON for a SET period of time. When the external switch is again closed, the UV system will remain on and the time OFF period is reset. This prevents system from swithcing ON and OFF during times of no flow.

4-20mA

The UV sensor monitors the uv irradiance and is tracked with a 4-20mA output. This can be displayed remotely

Standard Models up to 250m3 Per Hour

Model A250 A400 A600 A800 A1000 A1200 A1600 A2000 A2500
Flow Rate l/hr 25 000 45 000 60 000 80 000 100 000 120 000 160 000 200 000 250 000
No UV Lamps 2 2 4 4 6 6 8 8 8
UV Lamp Watts 400 640 800 1200 1200 1920 2560 2700 3200
Flange  (mm) 80 80 80 100 100 150 150 200 200
Chamber Material SS SS SS SS SS SS SS SS SS
Lamp Life 13000 13000 13000 13000 13000 13000 13000 13000 13000
Voltage 110/240 110/240 110/240 110/240 110/240 110/240 110/240 110/240 110/240
Circuit Breaker RCD RCD RCD RCD RCD RCD RCD RCD RCD
IP Rating 65 65 65 65 65 65 65 65 65
Electronic Ballast Standard Standard Standard Standard Standard Standard Standard Standard Standard
Lamp Alarm Standard Standard Standard Standard Standard Standard Standard Standard Standard
UV Sensor Standard Standard Standard Standard Standard Standard Standard Standard Standard
4-20mA Standard Standard Standard Standard Standard Standard Standard Standard Standard
Remote Switching Standard Standard Standard Standard Standard Standard Standard Standard Standard
Off-Delay Relay Standard Standard Standard Standard Standard Standard Standard Standard Standard
Alarm Contacts Standard Standard Standard Standard Standard Standard Standard Standard Standard
Mounting Brackets Standard Standard Standard Standard Standard Standard Standard Standard Standard
Hours counter Standard Standard Standard Standard Standard Standard Standard Standard Standard
Control Panel SS SS SS SS SS SS SS SS SS
Cabling All Cabling inclusive

 

INFRALiGHT-Genuine Ultraviolet Solutions